EL3001 Control Panel
Easy to install, complete monitoring system to detect early liquid leakage. Once leak is detected it responds within a few seconds and provides accurate leak location.
General Features
-
Maximum accumulated length of sensing cable
200m (Note: 192m for 4-20mA interface) -
Maximum accumulated length of jumper cable
300m -
Precision of leak location
+/- 1 metre or +/- 0.5% -
Display
LCD with backlight. 2 x 14 English characters -
Audible alarm
90dB max. buzzer with silencing button -
System reset
One single button for testing/resetting the system (hold down buzzer button for 6 seconds) -
Failsafe operation
Ability to operate in loop back operation and to detect liquid leakage during cable break -
Time to detect leak/cable break
4 seconds typically -
Liquid leak detection capability
Typically 20mm in length of liquid (e.g. tap water) in full contact with sensing cable. Leak sensitivity is adjustable. -
Multi-leak detection and location capability
-
Modbus TCP optional
-
Remote supervision by RS485 Modbus optional
-
Analog output 4-20mA interface optional
-
ASIC based digital location principle (patent pending) with inherent temperature stability, zero drift and very low power consumption
Environmental Ratings
Operating temperature | -10°C - 50°C (indoor installation only) |
Storage Temperature | -20°C - 70°C |
Humidity | 5% to 95% non-condensing |
Power Requirements
Power Supply | 230 +/- 15% VAC, 50/60 Hz |
Optional Input | 115 VAC/ 50-60 Hz or 12 to 30 VAC/DC power input |
Power Consumption | 3.5 VA / 3 W maximum |
Power Relays Switching Characteristics
Cable break/power failure by contact (1 relay) | Operation - SPDT Switching current - 3A at 250 VAC, 5A at 30 VDC |
Liquid leakage dry contact (2 relays) | Operation - SPDT Switching current - 5A at 250 VAC, 7A at 30 VDC |
Serial Communication Interface
Physical support | RS485-two wire, ESD and surge protected as per IEC 61000-4-5 |
Protocol | Modbus |
Optional | Modbus/TCP output with 10/100Mbs Ethernet and RJ-45 connector |
Analog Output
Physical support | 4 to 20 mA opto-isolated interface |
Voltage range | 9 to 36 VDC overvoltage protected |
Additional information | Two-wire opto-isolated analog current interface with galvanic separation of 2.5kV |
Nominal current | Normal - 4 mA |
Compliance to International Standards
EMC emission | IEC61000-6-3(2001) Electromagnetic compatibility Generic emission standard for residential, commercial and light industrial environment |
EMC immunity | IEC61000-6-1(2001) Electromagnetic compatibility Generic immunity standard for residential, commercial and light industrial environment |